Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM00117
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
03/25/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*NO CORRECTION HAVE BEEN MADE. RECALL FOR INSPECTION. | |
03/24/2003 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1.) CONDENSATE DRAIN TERMINATION INTO FLOOR DRAIN MUST HAVE AN AIR GAP & A TRAP. 2.) HOOK UP CONDENSATE DRAIN TO AC-2 ON ROOF. 3.) MARK UNIT DATA PLATES AS PER MANUFACTURERS INSTRUCTIONS ON DATA PLATE. SCRATCH OFF BOX MUST TO HEATER INSTALLED OR "NONE". FUSE DISCONNECTS ACCORDINGLY. DO NOT DISFIGURE THE FUSING REQUIREMENT ON DATA PLATE! |