Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T03CM00094
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2003 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
02/28/2003 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) HOLDOWNS WITH #16 SIGN REQUIRE EPOXY SET, CAN'T ACEPT WRONG BOLTS, ANYMORE 2) ANCHOR FRONT COLUMN TO SLAB 3) CORNER STUDS 2ND FLOOR FRONT POP OUT ADD STUDS OR BLOCK, TO STIFFEN 4) FRONT ENTRY BOTTOM PLATES NOT SECURED, NAIL SHEAR OSB FRONT ABOVE WINDOWS BAND BETWEEN FLOORS 8) STRAP REAR COLUMNS TO DECL 9) G-2 SHEARWALL IS BLOCKED WITH HEATER PLATFORM TO WINDOW 10) USE DETAIL 10/SD4 AT SHEARWALL INTERSECTIONS YOU NEED THE NAILING 11) NAIL OFF FLOOR DECK 12) ADD 2ND WIND BRACE AT REAR WALL 2ND FLOOR 13) WOULD LIKE TO TALK TO FRAMING FOREMAN |