Permit: T03CM00074

Parcel: 10821328A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
07/14/2003 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
07/02/2003 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection 0999*/ 1) OVERFLOW, AUX. DRAIN PAN UNDER EVAP. COILS ?? 2) BE SURE TO COMPLETE ELECTRIC ? PLATE ON SUSPENDED AIR HANDLER. AUX. HT STRIP ? YES? NO? NONE? WHAT SIZE? 3) HOLED IN PLENIUMN BEING ISOLATED FROM SIDE W/EXPOSED WOOD AND INSULATED ?
05/08/2003 MECHANICAL - ABOVE CEILING Partial Approval NEW UNIT.
1.) MAINTAIN CLEAR ACCESS TO AIR HANDLER.
2.) CONDENSATE & OVER FLOW PAN, DRAINS.