Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T03CM00051
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2004 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection 0000* | |
02/19/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection 0000*/ 1) NEUTRALS AND GROUNDS REVERSED IN PANEL 2) CONNECT BLDG STEEL BOND TO SERVICE 3) PLEASE PROVIDE A LETTER FOR CHANGES TO PLANS-OUTLETS MOVED OR DELETED, VERIFY A.C. RATING, DELETE FUTURE BARN 4) UFER AT MAIN SERVICE ON PLAN 1/0 WE HAVE #4 INSTALLED 5) INSTALL LABEL FOR NO WATER BOND 6) OK CABLE DROP ONLY |