Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM00051

Parcel: 133070010


Addresses:

2200 N LA RIENDA AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T03CM00051

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2004 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*
02/19/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) NEUTRALS AND GROUNDS REVERSED IN PANEL 2) CONNECT BLDG STEEL BOND TO SERVICE 3) PLEASE PROVIDE A LETTER FOR CHANGES TO PLANS-OUTLETS MOVED OR DELETED, VERIFY A.C. RATING, DELETE FUTURE BARN 4) UFER AT MAIN SERVICE ON PLAN 1/0 WE HAVE #4 INSTALLED 5) INSTALL LABEL FOR NO WATER BOND 6) OK CABLE DROP ONLY