Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM00046
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/13/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
03/12/2003 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000* | |
03/07/2003 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) INSTALL HTT16'S AT FRONT DOOR 1 EPOXY BOLT, ALSO SHEARWALL AT (3) AND AT STAIR ATTIC KWK BOLT 2) BANG PLATE WATER LINES AT WATER HTR/WASHER TRAY WATER TOP PLATE 3) 7/12 PITCH ON WATER HEATER FLUE 60 DEGREE MINIMUM 4) NO DWV TEST 5) FINISH RETURN AIR 6) WATER HEATER FLU FIRE STOP 7) REROUTE GAS AT BOTH FURNACE 8) TUB BACKING 9) BANG PLATE 2ND FLOOR TOILET VENT 10) WIND BRACE CUT AT FRONT WALL 11) 5/SD2 AND 6/SD2 SHEAR PANEL NAILING GARAGE TO HOUSE WALL 12) SECURE TUB SURROUNDS |