Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T03CM00027
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/26/2003 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
02/25/2003 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) SANTEE BRACE CUT AT WEST WALL 2) DETAIL 15 PAGE A8 NOT PER PLAN REVISE TO SHOW AS BUILT AND APPROVED | |
02/24/2003 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) 2ND FLOOR FRONT WALL BELOW WINDOWS MISSING ON CENTER CRIPPLES 2) NAIL SHED ROOF EAST SIDE TO LEDGER/END RAFTER WITH 8D'S 3) MISSING WIND BRACING WEST SIDE 4) LEDGER INTERIOR NEEDS TO BE SUPPORTED AT JOINTS, NAILS MISSING IN ROOF TRUSS HANGERS 5) CHECK HEADER SIZE 2ND FLOOR EAST WINDOW 6) CHECK KITCHEN LEDGER SIZE 7) NAIL HORIZONTAL JOINTS AT SHEARWALL AT BALCONY 8) 2ND FLOOR CLOSET SHEAR TRANSFERS TWO NAIL TO ROOF 9) FRONT DOOR BOTTOM PLATES SECURE TO FLOOR 10) NAIL ALL SCISSOR TRUSS CLIPS TO TOP PLATE 11) NAIL SHEAR TRANSFER AT KITCHEN SOFFIT 12) LEDGER AT KITCHEN TO BE 2 X 8 ADD 2 X 4 FOR HANGER NAILS 13) NEED HANGERS AT 2 X 4 TOP CHORD GARAGE EXTENSION 14) CONNECT # 3 SHEAR WALL TO ROOF 15) 2 X 4 BOTTOM PLATE OVER SHEAR BOX PANELS NAIL WITH 10D'S 8" ON CENTER 16) WALKING DECK LEDGER CONNECTION 15/A8 |