Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM00019
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/29/2003 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
12/12/2003 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) IMC 306.5 NEED PERM LADDER IN RECESSED AREA OF ROOF WHERE UNITS 3, 4 AND 5 ARE LOCATED. PARAPET WALL IN EXCESS OF 30" INTERFERS WITH ACCESS 2) COND. PIPING OPEN VENT FOLLOWS TRAP, DOES NOT LOCATE AHEAD OF IT |