Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM00019
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*/1) SOIL WATER TEST IS OK. 2) OK FOR DRYWALL UPON BLDG INSPECTION APPROVAL. | |
09/30/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) AIR PRESSURE TEST 50 POUNDS FOR WATER DISTRIBUTION IS-OK 2) OVERHEAD WATER DISTRIBUTION IS OK 3) NOTE: WILL HAVE TO RELOCATE OVERHEAD AWAY FROM ELECTRICAL PANEL 4) NOTE: HAD A METTING WITH PROJECT SUPERINTENDENT ON ADDING DISHWASHER AND P.O.C. OK FOR INSTALLATION AS PER TRINI |