Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR SPACE #101,115 AND OWNERS METER. OK CABLE DROP OK C OF O PLEASE NOTE THAT BLD. HAD POWER PREIVOUSLY TO SERVICE UPGRADE. | |
| 03/19/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1.) CAP OFF UNUSED ROMEX AND TERMINATE IN APPROVED J-BOX INSTALL MISSING COVERS. 2.) BOND WATER LINE TO BACK SERVICE, WIRE SIZE TO COMPLY WITH ART 250 NEC. (104). 3.) USE CLAMP TYPE CONNECTOR TO TERMINATE GROUNDING ELECTRODE CONDUCTORS TO GUTTER. 1/2" EMT CONNECTORS NOT LISTED FOR USE SEE ART 110-3. ART 300 WIRING METHODES 4.) NEED REVISION FOR OUTSIDE LIGTH CIRCUITING. (ARCH). |
|
| 03/18/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) NO COMPLIANCE WITH NOTE #1,8, NOTES #1 INSP. 2-5-03. 2.) GROUNDING ELECTRODE CONDUCTOR NOT SIZED PROPERLY. 3.) BOND WATER & GAS LINES. 4.) A RE INSP. FEE WILL BE ASSESED NEXT INSP. IF NO COMPLIANCE. |
|
| 03/14/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) GET APPROVED REVISIONS FOR FEEDERS FROM PNL A & B BEING REDUCED NOT 4/0'S 2.) UFER AT SERVICE TO BE CONNECTED TO 2 GROUND RODS, STRAP BONDS TO GAS & WATER. 3.) RUN A MAIN BONDING JUMPER #/20 TIE NEUT & UFER. 4.) RING REVISE TO GROUND BUSHING AT J-BOX BEFORE GUTTER. 5.) PANEL O CONTAINS NO CIRCUITS AS PLAN CALLS FOR 6.) ICE MACHINE HAS NO RECEPTACLE. 7.) HOW ARE COOLER & EXFAN INTERLOCKED 8.) HOOD LIGHTS TO BE CONNECTED. 9.) LIGHTS ON ROOF NOT CONNECTED NOR SUPPORTED. 10.) EX FANS WIRING HAS TO BE CONNECTED PROPERLY. 11.) ROOF LIGHTS TO BE RUN TO O PNL 12.) SIGN CIRCUIT TO BE RUN TO O PNL 13. OUTSIDE LIGHTS UNDER REMOVED CANOPY TO BE OMMITTED? 14.) UPDATE PANEL SCHEDULES. 15. FIX O5 WALL LIGHTS. 16.) PLEASE GO THUR ALL EXISTING ITEMS TO VERIFY ALL ELECTRICAL IS INTACT. |
|
| 03/12/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* NOTES 1.) OUTSIDE WALL LIGHTS NOT INSTALLED, WIRING NOT COMPLETE LEAVE TILES OPEN WHERE WORK DONE FOR INSP. 2.) NO PANEL SCHEDULE, MISSING BREAKER BLANKS, 3.) MISSING J-BOX COVER BY WATER HTR ROOM. 4.) BOND BUSHINGS REQUIRED FOR NIPPLES AT ALL LINE OR UTILITIES CONDUCTORS. 5.) PLUG UNUSED OPENINGS. 6.) SHEET METAL SCREWS NOT ALLOWED FOR ATTACHMENT OF GROUND LUGS, SCRAPE OF ENAMEL. 7.) UTILITIES & CUSTOMER LOAD SERVICE CONDUCTORS NOT ALLOWED IN SAME ENCLOSURE PER 230 NEC. 9.) OUTSIDE LIGHTS TO COMPLY WITH CITY LTG ORDIN. 50 WATTS MAX UNLESS SHIELDED. |