Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM00001
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
04/15/2003 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) NAIL PROTECT SHOWER VENT AT TOP PLATE 2) PEX PLUMBING NOT ALLOWED WITHIN 12" OF RECESSED LIGHT BATH 3) FIRE BLOCK MISSING SOUTH EAST CORNER 4) INCORRECT HANGERS ON GLU LAM BEAM, NOT BEARING OR NAILED 5) SMOKE DETECTOR NOT TIED TO EXISTING AND SMOKE DETECTOR IN BREAKFAST ROOM NOT INSTALLED 6) ANCHOR BOLTS LOOSE 7) NO WATER TEST ON DRAIN WASTE VENT SYSTEM PER UPC 712.2 | |
04/03/2003 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) GROUND ALL ELECTRIC BOXES 2) BANG PLATES MISSING 3) BLOCK 3 SIDES AIR GRILL 4) INSTALL STUCCO MESH PRIOR TO FRAMING APPROVAL |