Permit: T03BU02984

Parcel: 13405119M


Addresses:

9491 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/20/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
02/19/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ PLEASE - A SEAL OFF IS REQUIRED AT ALL CONDUITS LEAVING THE PUMP MOTER UNLESS LISTED AS 'FACTORY SEALED, NO SEAL OFF REQUIRED.'
02/18/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999$
01/23/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ L.B. FITTING AFTER EYS INCORRECT. NEED EYS WITHIN 18" OF MOTOR AT DISCONNECT SWITCH CONDUIT. SWITCHED WIRED?/ PROVIDE 1-4 ABOVE. PROVIDE INFO ON CIRCUIT FOR CONDUIT RUN
01/13/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) DO 1-4 OF PRIOR NOTICES BEFORE NEXT INSPECTION. 2) NEED SEAL OFF AT THE 20' RADIUS LEAVING THE CL. I, DIV 2 AREA INTO UNCLASSIFIED AREA. 3) PUMP MOTOR: SEAL OFF REQUIRED [BOTH CONDUIT] WITHIN 18" OF EX. PROOF T.B. AND NO UNAPPROVED FITTINGS IN BETWEEN. 4) DO DISCONNECTS DISCONNECT NEUTRAL?