Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/20/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/19/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ PLEASE - A SEAL OFF IS REQUIRED AT ALL CONDUITS LEAVING THE PUMP MOTER UNLESS LISTED AS 'FACTORY SEALED, NO SEAL OFF REQUIRED.' |
| 02/18/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999$ |
| 01/23/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ L.B. FITTING AFTER EYS INCORRECT. NEED EYS WITHIN 18" OF MOTOR AT DISCONNECT SWITCH CONDUIT. SWITCHED WIRED?/ PROVIDE 1-4 ABOVE. PROVIDE INFO ON CIRCUIT FOR CONDUIT RUN |
| 01/13/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) DO 1-4 OF PRIOR NOTICES BEFORE NEXT INSPECTION. 2) NEED SEAL OFF AT THE 20' RADIUS LEAVING THE CL. I, DIV 2 AREA INTO UNCLASSIFIED AREA. 3) PUMP MOTOR: SEAL OFF REQUIRED [BOTH CONDUIT] WITHIN 18" OF EX. PROOF T.B. AND NO UNAPPROVED FITTINGS IN BETWEEN. 4) DO DISCONNECTS DISCONNECT NEUTRAL? |