Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/17/2003 |
ELECTRIC - TEMPORARY SERVICE |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 12/18/03AM |
| 12/16/2003 |
ELECTRIC - TEMPORARY SERVICE |
|
Partial Approval |
IVRS - Inspection 0000* THE GROUNDING ELETRODE CONDUCTOR IS REQUIRED TO TERMINATE AT THE NEUTRAL- NEUTRAL BUS BAR NOT THE EQUIP GROUNDING BUS BAR. (SEE N.E.C.) |
| 12/15/2003 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999* INSTALL BREAKER(2 POLE CUTLER HAMER 125 AMP.) TERMINATE EQUIP GROUNDING CONDUTOR. INSTALL PROTECTIVE BUSHING AT SEALTIGHT CONNECTORS. |
| 12/09/2003 |
ELECTRIC - TEMPORARY SERVICE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 12/08/2003 |
ELECTRIC - TEMPORARY SERVICE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |