Permit: T03BU02869

Parcel: 114474850

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T03BU02869

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
12/17/2003 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection 0000*SENT TO TEP ON 12/18/03AM
12/16/2003 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection 0000* THE GROUNDING ELETRODE CONDUCTOR IS REQUIRED TO TERMINATE AT THE NEUTRAL- NEUTRAL BUS BAR NOT THE EQUIP GROUNDING BUS BAR. (SEE N.E.C.)
12/15/2003 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999* INSTALL BREAKER(2 POLE CUTLER HAMER 125 AMP.) TERMINATE EQUIP GROUNDING CONDUTOR. INSTALL PROTECTIVE BUSHING AT SEALTIGHT CONNECTORS.
12/09/2003 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection 0000*
12/08/2003 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection 0000*