Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T03BU02869
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/17/2003 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection 0000*SENT TO TEP ON 12/18/03AM | |
12/16/2003 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection 0000* THE GROUNDING ELETRODE CONDUCTOR IS REQUIRED TO TERMINATE AT THE NEUTRAL- NEUTRAL BUS BAR NOT THE EQUIP GROUNDING BUS BAR. (SEE N.E.C.) | |
12/15/2003 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0999* INSTALL BREAKER(2 POLE CUTLER HAMER 125 AMP.) TERMINATE EQUIP GROUNDING CONDUTOR. INSTALL PROTECTIVE BUSHING AT SEALTIGHT CONNECTORS. | |
12/09/2003 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection 0000* | |
12/08/2003 | ELECTRIC - TEMPORARY SERVICE | Not ready for Inspection | IVRS - Inspection 0000* |