Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2004 | FIRE SPKLR - FINAL | Approved | ||
| 03/04/2004 | FIRE SPKLR - FINAL | Denied | 1. Replace painted fire sprinklers, remove tape from sprinklers. 2. Install sprinklers in walk-in refrigerators/freezers. 3. Rotate branchline in storage area so that sprinklers are in correct position. |
|
| 02/18/2004 | FIRE SPKLR - FINAL | Denied | Need plan submittal/permit for fire sprinkler protection under exterior storage canopy. |