Permit: T03BU02794

Parcel: 130071040


Addresses:

3755 E JUAREZ ST

Inspection Status: Approved

Inspection History: POOL/SPA FINAL/BARRIER

Date Description Inspector Results Comments
01/27/2004 POOL/SPA FINAL/BARRIER Approved IVRS - Inspection 0000*
01/23/2004 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection 0999*/ 1) NO ONE HOME
01/12/2004 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection 0999*/ 1) ELECTRIC OVERHEAD SERVICE MUST BE AT LEAST 10 FEET HORIZONTALLY FROM EDGE OF POOL 2) GATE MUST BE SELF CLOSING AND LATCHING 3) GATE LATCH MUST BE 54" ABOVE WALKING SURFACE 4) SOUTH WEST CORNER OF BARRIER HAS MORE THAN 4" CLEARANCE
01/07/2004 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection 0999*/ 1) MAXIMUM 4" CLEARANCE UNDER ENCLOSURE FENCE 2) MAXIMUM 4" SPACING BETWEEN METAL VERTICAL BARS AND BLOCK WALL 3) UNCOVER ELECTRIC FROM MAIN PANEL TO POOL EQUIPMENT PER PREVIOUS REQUEST 4) ELECTRIC CODE FOR POOLS REQUIRES MINIMUM 10' HORIZONTAL CLEARANCE FROM POOL TO OVER HEAD CONDUITS (APPROX 7' EXISTING)