Permit: T03BU02792

Parcel: 13707045D


Addresses:

251 W IRVINGTON RD


Inspection Status: Approved

Inspection History: GRADING - FINAL

Permit Number - T03BU02792

Inspection Description - GRADING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2008 GRADING - FINAL Approved Contractor addressed punch list, provided letter from engineer.
02/04/2008 GRADING - FINAL Denied Contractor needs to provide drainage letter per Chapter XIV, Section 14.2 (7).
01/14/2008 GRADING - FINAL Cancelled IVRS - AP canceled
12/27/2007 GRADING - FINAL Cancelled IVRS - AP canceled
12/17/2007 GRADING - FINAL Cancelled IVRS - AP canceled
10/18/2007 GRADING - FINAL Not ready for Inspection Contractor paving parking area and striping.
02/22/2007 GRADING - FINAL Denied Spoke to contractor, only called in so permit would not expire.
02/21/2007 GRADING - FINAL Denied Punch List
1. Provide drainage on southeast corner of property. Water ponding in corner between block wall and building.
2. Install scuppers for roof drains. Roof drains draining across sidewalks and HC ramps.
3. Provide positive flow into detention basin. Water draining across sidewalk into street.
4. Clean all scuppers.
5. Clean bleeder pipe northside of property.
6. Stop water from flowing around wier. (detention basin) at sidewalk.
7. Remove rebar westside of property.
8. Clean all silt out of parking lot.
9. Repair/replace broken and missing curb stops.
10. Repair curb northeast corner of parking lot.
11. Paint bollards in trash enclosure.
12. Repair all erosion in basins.
13. Provide gates for trash enclosure. Per standard 6-01.0.
14. Stop water from ponding in trash enclosure.
15. Stop ponding in middle of parking lot.
16. Install curb southwest corner of parking lot.
17. Provide letter from engineer, certify all detention basins and drainage ways. Per Chapter XIV, Section 14.2(7)
02/21/2007 GRADING - FINAL Cancelled IVRS - AP canceled
02/20/2007 GRADING - FINAL Denied Contractor needs to address punch list.
02/16/2007 GRADING - FINAL Cancelled IVRS - AP canceled
11/16/2006 GRADING - FINAL Not Applicable Met with Jim from La Causa Construction and Jim Femling on site. Walked site and went over punch list.
11/30/2004 GRADING - FINAL Denied 1) THE BASINS ON-SITE HAVE NOT BEEN CONSTRUCTED AS SHOWN ON THE APPROVED.
2) THE WEIR OUTLET STRUCTURE FOR THE NORTHWEST BASIN HAS NOT BEEN CONSTRUCTED.
3) THE WATER HARVESTING BASIN WEST OF THE EAST PARKING LOT HAS NOT BEEN CONSTRUCTED AT THIS TIME.
4) A SECTION OF SIDEWALK HAS NOT BEEN CONSTRUCED AT THE SOUTHWEST CORNER OF THIS SITE.
5) REPAIR ALL DAMAGED SIDEWALKS AND WHEELCHAIR ACCESS RAMPS ON THIS SITE.
6) THE POST BARRICADES ADJACENT TO THE NORTHERN BASINS HAVE NOT BEEN INSTALLED AT THIS TIME.
7) THE GUNITE SLOPE STABALIZATION HAS NOT BEEN PROVIDED ON THE SOUTHSIDE OF THE NORTHERN BASIN.
8) ROOF DRAINAGE IS CURRENTLY BEING DEPOSITED ONTO THE SIDEWALK AT THE SE CORNER OF THE AMPHI THEATRE, THIS IS NOT ALLOWED.
CONTACT DAVID ROBERTS AT 349-7643 AND ARRANGE FOR AN ON-SITE MEETING TO DISCUSS ALL REMAINING ISSUES FOR THIS SITE.