Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
| Date |
Description |
Inspector |
Results |
Comments |
| 12/10/2003 |
POOL/SPA FINAL/BARRIER |
|
Approved |
IVRS - Inspection 0000* |
| 12/03/2003 |
POOL/SPA FINAL/BARRIER |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NEED BOND CONNECTORS ON ALL FENCE CONNECTIONS 2) BOND AIRATOR 3) JACCUZI, LIGHT PUT A COPPER CONNECTOR #8 CU, ON #8 CU WIRE ATTACH TO WET NICHE FIXTURE. LEAVE COMPOUND OFF CONNECTION 4) SECURE ALL SEAL TITE CONDUIT TO WALL, ALL CONDUIT OFF THE GROUND |