Permit: T03BU02485

Parcel: 13610023L


Addresses:

2601 S HOUGHTON RD


Inspection Status: Approved

Inspection History: GRADING - FINAL

Permit Number - T03BU02485

Inspection Description - GRADING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/16/2005 GRADING - FINAL Approved FINAL GRADING INSPECTION HAS BEEN APPROVED. ALL PRIOR PUNCH LIST ITEMS HAVE BEEN ADDRESSED AND CORRECTED. NO OTHER CONCERNS EXIST FOR THE FINAL GRADING APPROVAL.
02/11/2005 GRADING - FINAL Correction Required Final grading will be approved upon completion and reinspection of the following punch list items: 1) No bicycle parking structure as per Development Plan, detail 9/3, and General Site Note #6. 2) Wall opening located on the North side of the parking lot not constructed IAW Grading Plan detail 12/5. Rock at the wall opening needs to be flush with the depressed curb as shown in the Grading Plan detail 17/5. 3) The bubbler located on the Southeast corner of the property needs to be built as per Grading Plan detail 16/5. 4) No drive through sign as shown on Grading Plan. 5) Repair erosion damage to the East slope of the detention basin located on the far Southeast side of the property. 6) Remove plastic sheeting from the catch basin located on the North side of the property. 7) The catch basin on the Southwest corner of the property is not constructed as per Grading Plan detail 21/5.