Inspection History: POOL/SPA PRE-GUNITE
Permit Number - T03BU02209
Inspection Description - POOL/SPA PRE-GUNITE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2003 | POOL/SPA PRE-GUNITE | Approved | IVRS - Inspection 0000*/ 1) NOTES: WEST POOL WALL IS NOT APPROVED FOR RETAINING 2) DRAINAGE METHOD TO MEET ENGINEERED GRADING PLAN FOR THIS SITE 3) RIP RAP TO BE RESTORED TO ORIGINAL STATE | |
| 10/28/2003 | POOL/SPA PRE-GUNITE | Denied | IVRS - Inspection 0999*/ 1) NOTES: THE STEEL IN THE FREE STANDING WALL IS CORRECT FOR A FREE STANDING WALL 2) THE HEIGHT EXCEEDS THE 2' SHOWN ON PLAN, THIS EXCEEDS THE ENGINEERING 3) IRREGARDLESS OF THE FREE STANDING WALL, I SEE NO PLAN FOR RETAINING THE SOIL, ROCK ON THE WEST SIDE OF THE POOL | |
| 10/16/2003 | POOL/SPA PRE-GUNITE | Denied | IVRS - Inspection 0999*/ 1) RETAINING WALL WILL BE REQUIRED FOR WEST. SUBMIT PLANS TO CITY OF TUCSON FOR APPROVAL | |
| 10/10/2003 | POOL/SPA PRE-GUNITE | Partial Approval | IVRS - Inspection 0000*/ 1) NOTE: DO NOT GUNITE UNTIL CITY HAS APPROVED WEST AS A RETAINING WALL FOR FREE STANDING POOL WALL | |
| 10/02/2003 | POOL/SPA PRE-GUNITE | Denied | IVRS - Inspection 0999*/ 1) ADDITIONAL REINFORCEMENT REQUIRED AT AREAS WITHIN 45 DEGREE ANGEL OF PORCH. (PORCH IS 2' FROM EXCAVATION) 2) RETAINING WALL WILL BE NEEDED AT REAR OF FREE STANDING POOL WALL 3) INSTALL CROSS BRACING AT LIGHT FIXTURE 4) 3/4" CLEARANCE AT STEEL TO PLUMBING 6) 3" CLEARANCE AT STEEL TO SOIL |