Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
Permit Number - T03BU01900
Inspection Description - POOL/SPA FINAL/BARRIER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/21/2003 | POOL/SPA FINAL/BARRIER | Approved | IVRS - Inspection 0000* | |
11/05/2003 | POOL/SPA FINAL/BARRIER | Partial Approval | IVRS - Inspection 0000*/ 1) WET NITCH FIXTURE BOND COVERING NOT VERIFIED 2) 2 SCREWS MISSING IN POOL LIGHT J-BOX 3) SCREW AT WINDOW TO BE NON-REMOVEABLE | |
10/02/2003 | POOL/SPA FINAL/BARRIER | Cancelled | IVRS - Ri canceled | |
09/24/2003 | POOL/SPA FINAL/BARRIER | Partial Approval | IVRS - Inspection 0000*/ 1) RAISED DECK: POOL CODE SEC. 316.4 A) A SUITABLE HAND TO BE INSTALLED, NO MORE THAN 12" ABOVE WATER LINE B) NEED TO COMPLETELY COVER BOND CONNECTION IN WET NICHE FIXTURE WITH POTTING COMPOUND | |
09/10/2003 | POOL/SPA FINAL/BARRIER | Partial Approval | IVRS - Inspection 0000* |