Permit: T03BU01816

Parcel: 12801003A


Addresses:

240 S WILMOT RD


Inspection Status: Approved

Inspection History: STORMWATER FOLLOW-UP INSP

Permit Number - T03BU01816

Inspection Description - STORMWATER FOLLOW-UP INSP

Inspection Status - Approved

Date Description Inspector Results Comments
09/20/2006 STORMWATER FOLLOW-UP INSP Approved
07/13/2004 STORMWATER FOLLOW-UP INSP Partial Approval This site needs maintenance regarding the SWPPP plan. I met wit Ric Hic superintendent for the project and informed him of the needed maintenance. A punch list is provided below:
1. Repair or replace all silt fencing along the NW, NE, SE and East sides of the project.
2. Baracade non-stabilized entrance located on the NW end of the site.
3. Stabilze N. entrance as soon as possible.
4. Designate a concrete wash-out area.
5. Clean and remove all sediment in the street along
the North side of the site and also the West end leading
into the Park Mall parking lot.
6. Have stock piles watered down for dust control.

* Request for reinspection as soon as possible to verify corrective measures have been taken.
06/08/2004 STORMWATER FOLLOW-UP INSP Partial Approval For this site, I needed to go above and speak with Bobby, (general manager) regarding the L.A. Fitness sight on wilmot. I advised him of the fact that this site has not been kept up with its SWPPP controls. He did address this with Ric Hic who is in charge of the site. It has had an improvement since the last inspection and will be re-inspected as progress developes.