Permit: T03BU01801

Parcel: 141195680

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
07/29/2003 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection 0000*
07/17/2003 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection 0999*/ 1) SLAB POURED BEFORE INSPECTION 2) IT DOES NOT APPEAR THAT POST FOOTINGS WERE INSTALLED. YOU WILL TO DIG OUT ALONG EDGE OF SLAB TO EXPOSE SIDES OF FOOTINGS 3) ANCHOR BOLTS FOR SIMPSON POST BASES WERE ALSO NOT INSTALLED. YOU WILL NEED TO USE AN APPROVED WEDGE ANCHOR OR EQUIVALENT