Inspection Status: Denied
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/10/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) LAG BOLTS THROUGH CENTER OF 2 X 6 LEDGER ARE SPACED AT RANDOM INTERVALS OF 1'9" TO 3'8". 2) 2 X 6 RAFTERS SPAN 10'6" @ 24" O.C. 3) LEDGER HAS BEEN ATTACHED TO FACE AT STUCCO/FOAM (2" THICK TOTAL) THEREFORE 16d SINKERS AT ENDS OF LEDGERS DO NOT PENETRATE FRAME. 4) POST CAPS (SIMPSON AC4R)ARE ON ONE SIDE OF POST ONLY WITH 4 NAILS INTO POST AND 6 NAILS INTO BEAM. 5) IT IS UNKNOWN IF THER ARE FOOTINGS UNDER POSTS. |