Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T03BU01068
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2003 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection 0000*/ 1) NEW 20 AMP CIRCUIT FOR ? NOT IN PANEL A AS SHOWN ON PLAN 2) THE SEAL OFF BEFORE SWITCH INSIDE PUMP COMPARTMENT IS NOT FILLED 3) OPEN OR LOOSEN OTHER SEALS TO VERIFY COMPOUND 4) PLAN SHOWS ANS EMERGENCY SHUT OFF SWITCH USED TO DISCONNECT POWER SOURCE TO TANK, AN EMERGENCY TYPE MUSHROOM (RED) SWITCH TO BE USED-NOT NON RATED THROW SWITCH, (TANK ONLY 19' FORM SWITCH) 5) INSTALL A SIGN ON EMERGENCY SWITCH INDICATING EMERGENCY SHUT OFF SWITCH TO PROPANE TANK 6) PROVIDE VERIFICATION OF SWITCHING CIRCUIT FROM PANEL A TOC PANEL A HAS ALREADY BEEN CALCULATED FOR THIS LOAD |