Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
| Date |
Description |
Inspector |
Results |
Comments |
| 07/08/2003 |
POOL/SPA FINAL/BARRIER |
|
Approved |
IVRS - Inspection 0000* |
| 07/07/2003 |
POOL/SPA FINAL/BARRIER |
|
Not ready for Inspection |
ITEMS 1 & 2 NOT DONE FROM LAST INSPECTION |
| 07/02/2003 |
POOL/SPA FINAL/BARRIER |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NEED BETTER BONDING SUB-PANEL=SERVICE PANEL CONDUIT CONNECTION 2) WET-NICHE FIXTURE, #8 BOND WIRE CONNECTION IN FORMING SHELL NOT COVERED WITH APPROVED MATERIAL TWO LIGHTS DON'T FILL POOL 3) SUPPORT RING IN NON METALLIC CONDUIT AT LIGHT J-BOX |