Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03BU00593
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/03/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
03/26/2003 | FRAMING | Denied | IVRS - Inspection 0999* 1.) LEDGER HAS BEEN LAGGED WITH 1/4 INCH SCREWS. PLAN CALL FOR 3/8" LAG SCREWS. 2.) YOU MAY NOT ATTACH LEDGER TO OUTSIDE OF STUCCO & FOAM. YOU NEED TO MAKE A POSITIVE ATTACHMENT TO 2 X 6 FRAME WALL. |