Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
Permit Number - T03BU00555
Inspection Description - POOL/SPA FINAL/BARRIER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2003 | POOL/SPA FINAL/BARRIER | Approved | IVRS - Inspection 0000* | |
06/02/2003 | POOL/SPA FINAL/BARRIER | Partial Approval | IVRS - Inspection 0000*/ 1) I.R.C. SEE LAST INSPECTION 2) E4106.9.2 ALSO N.E.C. UNDER WET NICHE FIXTURES ENCAPSULATE | |
05/28/2003 | POOL/SPA FINAL/BARRIER | Partial Approval | IVRS - Inspection 0000*/ 1) BOND J-BOX FOR LIGHT BOTTOM OF BOX HAS TERMINAL-SEE CODE, ALSO ENCAPUSATE CONNECTION, INSIDE WEST NICHE FIXTURE | |
05/15/2003 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection 0999*/ 1) OWNER DOESN'T WANT POWER PULLED FROM J-BOX FOR POOL # SPA IS 30 AMPS TOTAL, IT'S OK CODE WISE PLEASE CLEAR THIS WITH OWNER 2) BOND METAL FENCE, JUMPER ACROSS GATE 3) SECURE J-BOX IT'S LOOSE 4) SUB-PANEL NOT ATTACHED TO WALL 5) WATER LINE TO BE 12" BELOW GRADE OR UNDER SLAB 6) TURN BACK FLOW DEVICE 180 DEGREE MOVE WATER LINE TO WEST SIDE OF DEVICE 7) INSTALL BUSHING AT BACK OF SUB-PANEL WHERE FEEDERS ENTER CAN | |
04/30/2003 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection 0999*/ 1) WATER LINE AND ANTI-SIPHON VALVE NOT HOOKED UP EXPOSE ENTIRE WATER LINE FOR INSPECTION 2) SUB-PANEL NOT COMPLETE, ELECTRICAL TO JACUZZI NOT COMPLETE |