Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
| 03/27/2003 | FRAMING | Denied | IVRS - Inspection 0999* 1.) FRAMING OF CARPORT DOES NOT CONFORM TO PLANS. 2.) SHEETROCK SCREWS MAY NOT BE USED TO ATTACH H2.5. CLIPS. USE "TICO" OR #10D NAILS OR HANGER SCREWS. 3.) A35 HANGERS REQUIRED FROM HOUSE JOIST TO REAR PORCH LEDGER. 4.) PLANS FOR REAR PORCH CONFLICT AS TO WHAT SIZE BEAM SHOULD BE IS IT 4 X 8 ON 4 X 8 OR 4 X 6? |