Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*OK WALLS & CEILING. | |
| 03/18/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* 1.) APPROVED LISTED CONNECTORS MUST BE USED TO TERMINATE MC CABLE IN AN APPROVED J-BOX. 2.) ALL J-BOX MUST BE ACCESABLE AFTER DRYWALL OR SIDING INSTALLED. 3.) WHEN TERMINATING CABLE IN BOXES THERE MUST BE AT LEAST 6" OF CONDUCTOR FOR MAKE UP. 4.) PLUG UNUSED OPENINGS IN J-BOX. PLEASE LEAVE PLAN/PERMIT ON SITE FOR INSPECTORS. |