Case: T02VL02486

Parcel: 112071090


Addresses:

2719 E WATER ST

Inspection Status: Correction Required

Inspection History: INITIAL CODE VIOLATION

Date Description Inspector Results Comments
01/02/2003 INITIAL CODE VIOLATION Correction Required 12/30/02, VISITED SITE, TOOK PICTURES, MET WITH BILLY RHOADS (RESIDENT) ON SITE, RESIDENT SHOWED ME SEVERAL ISSUES, MAIN ONE WAS THAT THE HEATER DOES NOT HEAT HOUSE, HEATER DOES WORK BUT IT IS UNDER SIZED TO HEAT ALL OF HOUSE, HEATER HAS BEEN REPLACED AT ONE TIME, OLD UNIT HAD A WALL THERMOSTAT AND STILL HAS THERMOSTAT WIRES IN PLACE, THE REPLACEMENT HEATER DOES NOT USE THERMOSTAT WIRES IT HAS A KNOB ON THE UNIT ITSELF, THIS SHOWS UNIT HAS BEEN REPLACED, ( W.O.P), ALSO GAS LINE COMES UP THROUGH SLAB FLOOR, CHECKED PANEL BOX AND FOUND THAT 3 FUSES ARE OVER SIZED, 3 ARE 30 AMP. FUSES, SHOULD BE 15 TO 20 AMP. ALSO OUTSIDE PANEL BOX HAS ONLY 1 30 AMP BREAKER, WHEN TALKING TO RESIDENT HE EXPLAINED THAT IN THE SUMMER SEASON HE HAS TO PLUG THE COOLER IN BY EXTENSION CORD TO MAKE IT WORK, GFCI IN KITCHEN SHOWS OPEN GROUND, AS DO OTHER OUTLETS, CABLE CO. HAD COME OUT TO CONNECT CABLE BUT COULD NOT DUE TO NO GROUNDING TO UNIT, WATER HEATER IN REAR OF UNIT HAS NO ENCLOSER, NO SHUT OFF VALVE, WASHING MACHINE DRAINS OUT TO GROUND, NOT HOOKED UP TO SANITARY SEWER, FRONT ENTRY DOOR HINGES DO NOT HOLD DOOR UP HAVE TO LIFT UP ON DOOR TO CLOSE AND WEATHER PROTECTION AROUND DOOR DETERIORATED AND OR LACKING, ALSO WEATHER PROTECTION AROUND REAR DOOR DETERIORATED AND OR LACKING, N.O.V. TO FOLLOW.