Case: T02VL02204

Parcel: 107142350


Addresses:

209 W GRANT RD

Inspection Status: Correction Required

Inspection History: INITIAL CODE VIOLATION

Date Description Inspector Results Comments
10/17/2002 INITIAL CODE VIOLATION Correction Required UNIT 206-1 - UHC 701.3 AND TFC 605.1 - ELECTRICAL HAZARDS - THERE IS EXPOSED ELECTRICAL WIRING IN THE BATHROOM. THERE ARE SPLICED ELECTRICAL WIRES AND EXTENSION CORDS POWERING THE SWAMP COOLER. THERE ARE NUMEROUS EXTENSION CORDS BEING USED THROUGH OUT THE UNIT ON A PERMANENT BASIS DUE TO LACK OF ELECTRICAL OUTLETS.

206-1 UHC 1001.8 - FAULTY WEATHER PROTECTION - ALL EXTERIOR DOORS LACK REQUIRED WEATHER PROTECTION AND HAVE BROKEN OR MISSING HARDWARE. BROKEN, LOOSE OR CRACKED GLASS THROUGHOUT THE UNIT. DETERIORATED, CRUMBLING OR LOOSE PLASTER IN SEVERAL AREAS OF UNIT.

206-1 TFC 1003.3.1.8 -ESCAPE AND RESCUE- THERE IS PLYWOOD BLOCKING WINDOWS AND DOORS.

206-1 UHC 901 TFC 907.2.10.1.2 SMOKE DETECTORS - THE UNIT LACKS REQUIRED SMOKE DETECTORS.

206-1 UHC 701.1 HEATING - THE HEATING SYSTEM IS NOT HOOKED UP, VERY DIRTY AND APPEARS NOT MAINTAINED IN A SAFE CONDITION. THE UNIT HAS A SMALL AMOUNT OF BTU'S FOR THE SIZE OF THE UNIT AND APPEARS THAT IT IS NOT CAPABLE OF HEATING THE ENTIRE UNIT.

206-1 UHC 1001.2.4 INADEQUATE SANITATION - THERE IS NO HOT WATER IN THE UNIT.

206-UHC 1001.2.13 GENERAL DILAPIDATION OR IMPROPER MAINTENANCE - THERE IS RAW SEWAGE LEAKING FROM THE 2ND FLOOR UNIT INTO THE UNIT CAUSING CEILING DAMAGE. THE COOLER STAND IS UNSTABLE AND DILAPIDATED. THE FASCIA IS DILAPIDATED, ROTTEN AND DROPPING.

206-1 UHC 1001.11 TFC 1011.3 HAZARDOUS OR INSANITARY PREMISES - THE UNIT HAS A LARGE ACCUMULATION OF JUNK, GARBAGE AND DEBRIS THROUGHOUT THE UNIT AND IN THE EGRESS AREAS.

206-2 UHC 701.1 HEATING- THE FURNACE IS INOPERABLE.

206-2 UHC 1001.2.13 UHC 1001.2.7 INADEQUATE SANITATION - GENERAL DILAPATION OR IMPROPER MAINTENANCE - THE WINDOW FRAMES AND TRIM ARE ROTTEN AND FALLING. THE BATHROOM CABINETS ARE ROTTEN AND WATER DAMAGED. THE KITCHEN SINK IS ROTTEN, RUSTED OUT AND LEAKING. THERE IS NO EXHAUST FAN IN THE BATHROOM.

206-2 UHC 1001.5 HAZARDOUS ELECTRICAL - THE LIGHT IN THE BATHROOM IS BROKEN, HAS EXPOSED ELECTRICAL WIRING AND IS NOT WORKING. THE KITCHEN CEILING LIGHT FIXTURE IS BROKEN, HAS EXPOSED ELECTRICAL WIRING.

206-2 UHC 1001.6 HAZARDOUS PLUMBING THERE IS NO GAS SHUT OFF VALVE AT THE GAS STOVE. THE TOILET IS LEAKING.

206-2 UHC 1001.8 FAULTY WEATHER PROTECTION - THE ENTRY DOOR LACKS PROPER WEATHER STRIPPING. THE UNIT HAS BROKEN GLASS WINDOWS.

206-2 UHC 1001.8 UCADB 302.5 TFC 110.1.1 STRUCTURAL HAZARDS THE KITCHEN CEILING HAS WATER DAMAGE AND IS SAGGING. THE BATHROOM FLOOR IS VERY WEAK AND THE TOILET IS DROPPING.

206-2 TFC 110.1.1 UCADB 302.2 & 16 & 17 TFC 1008.11 UNSAFE CONDITIONS- THERE IS NO HANDRAILS ON THE STAIRS LEADING TO THE SECOND FLOOR. THE ROOF IS BEING USED FOR PURPOSES OTHER THAN WHAT IT WAS INTENDED FOR AND BECAUSE OF THE GARBAGE, JUNK, AND DEBRIS AND OTHER ACTIVITY ON THE ROOF, IT IS CAUSING AN UNDUE STRESS TO THE STRUCTURE. THE STAIRS DO NOT HAVE THE PROPER RISER AND TREAD RATIO.

208-1 UHC 1001.5 TFC 605.1 ELECTRICAL HAZARDS - THE EVAPORATIVE COOLERS IN THE UNIT HAVE SPLICED EXPOSED WIRING AND ARE BEING POWERED BY AN EXTENSION CORD. THE EXTERIOR LIGHT FIXTURE HAS EXPOSED ELECTRICAL WIRING. THE ELECTRICAL OUTLET AT THE COOLER IS SCORCHED. THE LIGHT IN THE KITCHEN AREA HAS EXPOSED ELECTRICAL AND BEING POWERED BY AN EXTENSION CORD. THE OUTLET IN THE KITCHEN IS SCORCHED.

208-1 UHC 801 TFC 1003.1.8 EXISTS, ESCAPE, AND RESCUE - BEDROOM #1 AND BEDROOM #2 HAVE NO EGRESS. THERE IS A HASP ON THE EXTERIOR DOOR.

208-1 UHC 1001.6 HAZARDOUS PLUMBING - THE WATER HEATER IS MISSING THE TPR VALVE LINE AND COLD WATER SHUT OFF VALVE. THE VENT FOR THE WATER HEATER IS LOOSE AND DETACHING. THE FAUCETS AND PIPING ARE LEAKING IN THE UNIT.

208-1 UHC 901 TFC 901.6 SMOKE DETECTORS - THE UNIT LACKS SMOKE DETECTORS.

208-1 UHC 1001.8 FAULTY WEATHER PROTECTION - THERE ARE BROKEN WINDOWS AND DOORS THROUGH OUT THE UNIT. THERE ARE PENETRATIONS IN THE EXTERIOR OF THE UNIT.

208-1 UHC 1001.2.13 UHC 505.6 UHC 601.3 TFC 110.1.1 GENERAL DILAPIDATION OR IMPROPER MAINTENANCE - THE COOLER STAND IS UNSATBLE AND DILAPIDATED. THERE ARE LARGE HOLES IN THE BATHROOM DOOR. THE PLASTER IS FALLING OFF THE UNIT AT THE FRONT DOOR. THE EXTERIOR WOODEN OVERHANG HAS WATER DAMAGE.

208-1 UHC 901 TFC 901.6 SMOKE DETECTORS - THE UNIT LACKS SMOKE DETECTORS.

208-1 UHC 1001.2.13 UHC 505.6 UHC 601.3 TFC 110.1.1 GENERAL DILAPIDATION OR IMPROPER MAINTENANCE - THE COOLER STAND IS UNSTABLE AND DILAPIDATED. THERE ARE LARGE HOLES IN THE BATHROOM DOOR. THE PLASTER IS FALLING OFF THE UNIT AT THE FRONT DOOR. THE EXTERIOR WOODEN OVERHAND HAS WATER DAMAGE.

208-1 UHC 701.1 HEATING - THE FURNACE IS NOT CONNECTED AND IN WORKING CONDITION.

208-2 UHC 1001.8 FAULTY WEATHER PROTECTION - THE ROOF IS LEAKING AND HAS CAUSED EXTENSIVE CEILING DAMGE THROUGHOUT THE UNIT. THERE ARE BROKEN WINDOWS AND DOORS.

208-2 UHC 701.1 HEATING - THE FURNACE IS NOT CONNECTED AND IN WORKING CONDITION.

208-2 UHC 701.4 VENTING - THERE IS NO VENTING SYSTEM IN THE BATHROOM.

280-2 UHC 1001.5 TFC 605.1 ELECTRICAL HAZARDS - THE LIGHT ON THE KITCHEN WALL HAS EXPOSED ELECTRICAL WIRING. THERE ARE ELECTRICAL EXTENSION CORDS BEING USED ON A PERMANENT BASIS.

208-2 UHC 801 TFC 1003.31.8 EXITS, ESCAPE AND RESCUE - THERE IS A HASP ON THE EXTERIOR DOOR.

208-2 UHC 901 TFC 901.6 SMOKE ALARMS - THE UNIT LACKS SMOKE DETECTORS.

208-2 UHC 1001.2.13 UCADB 302.16 TFC 110.1.1 GENERAL DILAPIDATION AND IMPROPER MAINTENANCE HAZARDS - THE ENTRY DOOR DOES NOT OPERATE PROPERLY. THE COOLER IS RUSTED OUT AND LEAKING THE STAND IS UNSTABLE. THE FENCING IS DILAPIDATED AND FALLING DOWN. THE EAVES ARE MISSING BIRD BOARDS IN SEVERAL AREAS. THE KITCHEN FAUCET AND SINK ARE LOOSE AND LEAKING.

ALL TFC 605.1 HAZARDOUS ELECTRICAL - UNITS ARE MISSING GLOBES AND OTHER LIGHT FIXTURE COVERS.

ALL TFC 505.1 ADDRESSING - THE PROPERTY AND UNIT MARKINGS DO NOT COINCIDE WITH CITY AND COUNTY RECORDS. THE BUILDING AND IDENTIFICATION NUMBERS ARE NOT VISIBLE FROM THE STREET.

ALL UHC 1001.11 TFC 110.1.1 HAZARDOUS OR INSANITARY PREMISES - THERE IS GARBAGE AND DEBRIS ON THE EXTERIOR PROPERTY AND INTERIOR OF ALL THE UNITS INCLUDING THE ROOF. OTHER INFORMATION CAN BE FOUND IN THE NOTICE AND ORDER.