Inspection History Details
Inspection Status: Violation
Inspection History: INITIAL CODE VIOLATION
Case Number - T02VL02149
Inspection Description - INITIAL CODE VIOLATION
Inspection Status - Violation
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2002 | INITIAL CODE VIOLATION | Violation | VISITED SITE, WALK UNIT WITH TENANT. MIN-HOUSING ISSUES FOUND (1) HALLWAY CARPET ALWAYS WET AFTER SHOWER IS USED, MASTER BATH ROOM SINK-NO HOT WATER.(2) HALLWAY BATH ROOM-DETERIORATING & CRUMBLING DRYWALL BY TUB. (3) 2-BEDROOM DOOR HINGES IN NEED OF ADJUSTMENT. (4) BROKEN WINDOW IN LIVING ROOM CHECK ALL WINDOW CRANKS FOR PROPER OPERATION (5) WASHING MACHINE VENT PIPE HAS BEEN ALTERD DUE TO NEW ROOF INSTALATION, MUST EXTEND 3' ABOVE ROOF.(6) REMOVE RECEPTICALS FROM BATHROOM LIGHT FIXTURES AND OR INSTALL G.F.I.C. OUTLETS. (7) REPLACE ALL NON-GROUNDED 3 PRONG OUTLETS THUR OUT UNIT. RESTORE ELECTRICAL POWER TO EAST WALL OF LIVING ROOM. (8) LATCH FOR SHELF CLOSING SHELF LATCHING GATE MUST BE ON THE INSIDE OF INCLOSEURE. WILL ISSUES N OF O TO OWNER. TOOK PICTURES. SPOKE WITH OWNER, HAS NOT BEEN ABLE TO MAKE ARRANGEMENTS WITH TENANT FOR CONTRACTOR TO CHECK PLUNBING.OWNER WILLING TO ABATE ALL VIOLATIONS, & WAS NOT AWARE OF ELECTRICAL PROBLEMS. WILL TRY TO HAVE CONTRACTOR DO INSPECTION BY 11-6-02. DO FOLLOW UP IN 30 DAYS. |