Inspection History Details
Inspection Status: Closed
Inspection History: FOLLOW UP CODE VIOLATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2003 | FOLLOW UP CODE VIOLATION | Closed | COMPLETE FINALED CLOSE OUT ORGINIAL GROUND WIRE FOUND & TIED TO MOTOR. | |
| 04/16/2003 | FOLLOW UP CODE VIOLATION | Denied | THE GROUND WIRE TO MOTOR NOT TO BE TIED TO ITS OWN GROUND ROD BUT TO POOL METER SYSTEM, REBAR OR STEEL USED IN POOL. FU 10DAYS . 4/28/03 |
|
| 03/28/2003 | FOLLOW UP CODE VIOLATION | Violation | ONE LAST ITEM REMAINS #8 COPPER TIE TO POOL GRID FROM NEW MOTOR LOCATION. FU 10 DAYS. 4/14/03 |
|
| 03/17/2003 | FOLLOW UP CODE VIOLATION | Violation | FOLLOW UP 3/28/03 | |
| 02/28/2003 | FOLLOW UP CODE VIOLATION | Violation | 11AM LEFT NOTE FOR MANAGER TO CONTACT ELECTRICAN. TO SET UP MEETING FOR REVIEW OF CORRECTION AT POOL. WORK HAS BEEN CONNECTED WILL MEET WITH ELECTRICAL CONTRACTOR TO REVIEW INSTALLATION FU. 10 DAYS. 3/17/03 |
|
| 02/21/2003 | FOLLOW UP CODE VIOLATION | Correction Required | FOLLOW PARTIAL OK SOME OF THE WORK CORRECTED. PLEASE GIVE ME THE PACKAGE ON NOTICE FU 5 DAYS. FOLLOW UP 2/28/03 |
|
| 02/10/2003 | FOLLOW UP CODE VIOLATION | Violation | 1.) ALL POOL EQUIPMENT TO BE IN WEATHER PROOF STATUS. 2.) INSTALL SWITCH TO MOTOR PROPERLY. 3.) REMOVE AUROMEX. 4.) BURY UF FEEDER. 5.) CONNECT MOTOR TO GROUND SYSTEM. 6.) LABEL PANEL. 7.) GFI POOL LIGHT PLEASE CORRECT RECALL FU. 10 DAYS. FOLLOW UP 2/21/03 |
|
| 01/04/2002 | FOLLOW UP CODE VIOLATION | Violation | TRANFER TO COMMERICAL INSPECTOR. |