Case: T02VL02079

Parcel: 13331162B


Addresses:

8750 E COOPER ST

Inspection Status: Closed

Inspection History: FOLLOW UP CODE VIOLATION

Date Description Inspector Results Comments
04/29/2003 FOLLOW UP CODE VIOLATION Closed COMPLETE FINALED CLOSE OUT ORGINIAL GROUND WIRE FOUND & TIED TO MOTOR.
04/16/2003 FOLLOW UP CODE VIOLATION Denied THE GROUND WIRE TO MOTOR NOT TO BE TIED TO ITS OWN GROUND ROD BUT TO POOL METER SYSTEM, REBAR OR STEEL USED IN POOL.
FU 10DAYS . 4/28/03
03/28/2003 FOLLOW UP CODE VIOLATION Violation ONE LAST ITEM REMAINS #8 COPPER TIE TO POOL GRID FROM NEW MOTOR LOCATION. FU 10 DAYS.
4/14/03
03/17/2003 FOLLOW UP CODE VIOLATION Violation FOLLOW UP 3/28/03
02/28/2003 FOLLOW UP CODE VIOLATION Violation 11AM LEFT NOTE FOR MANAGER TO CONTACT ELECTRICAN. TO SET UP MEETING FOR REVIEW OF CORRECTION AT POOL.
WORK HAS BEEN CONNECTED WILL MEET WITH ELECTRICAL CONTRACTOR TO REVIEW INSTALLATION FU. 10 DAYS. 3/17/03
02/21/2003 FOLLOW UP CODE VIOLATION Correction Required FOLLOW PARTIAL OK SOME OF THE WORK CORRECTED.
PLEASE GIVE ME THE PACKAGE ON NOTICE FU 5 DAYS. FOLLOW UP 2/28/03
02/10/2003 FOLLOW UP CODE VIOLATION Violation 1.) ALL POOL EQUIPMENT TO BE IN WEATHER PROOF STATUS.
2.) INSTALL SWITCH TO MOTOR PROPERLY.
3.) REMOVE AUROMEX.
4.) BURY UF FEEDER.
5.) CONNECT MOTOR TO GROUND SYSTEM.
6.) LABEL PANEL.
7.) GFI POOL LIGHT
PLEASE CORRECT RECALL
FU. 10 DAYS. FOLLOW UP 2/21/03
01/04/2002 FOLLOW UP CODE VIOLATION Violation TRANFER TO COMMERICAL INSPECTOR.