Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Correction Required
Inspection History: INITIAL CODE VIOLATION
| Date |
Description |
Inspector |
Results |
Comments |
| 09/29/2002 |
INITIAL CODE VIOLATION |
|
Correction Required |
TFD EMERGENCY CALL OUT FOR BUILDING FIRE. COMPRESSOR ROOM @ REAR OF BUILDING BURNED UP. ELECTRIC POWER LOCKED OUT TO ENTIRE SPACE BECAUSE PANELS NOT IDENTIFIED UNABLE TO ISOLATE COMPRESSOR EQUIPMENT. GAS LOCKED OUT DUE TO MAIN GAS LINES BEING SUPPORTED ON DAMAGED STRUCTURE. RISK OF COLLAPSE DAMAGE. G & L IMPORTS DAMAGE: FIRE LOCATION OF DAMAGE: COMPRESSOR BUILDING AT REAR (SOUTH) OF SPACE. BUILDING: 12' X 20' 2 X 4 FRAME WITH 1 X 8 SIDING 100% LOSS 12' X 20' 2 X 6 ROOF WITH 1 X 12 SHEATING 100% LOSS. ELECTRICAL DAMAGED APPROXIMATELY 28 TIMERS AND DISCONNECTS AND VARIOUS CONDUITS OF UNKNOWN TERMINATION. PLUMBING: GAS PIPING SUPPORTED ON BURNED OUT BUILDING SUFFERED POSSIBLE HEAT DAMAGED. MECHANCIAL: 6-8 COMPRESSORS AND A/C UNITS 100% DAMAGE. PERMIT REQUIRED TO REBUILD COMPRESSOR ROOM. PERMITS REQUIRED TO RE-CONNECT ELECTRIC AND GAS. LICENSED ELECTRICIAN WILL HAVE TO IDENTIFY CIRCUITS TO FRONT STORE FOR PARTIAL RECONNECT. DAMAGED GAS PIPE WILL NEED TO BE REPLACED AND RE-SUPPORTED FOR GAS RECONNECT. 10/25/02 |