Case: T02VL00486

Parcel: 12007255B


Addresses:

13 W DISTRICT ST

Inspection Status: Approved

Inspection History: FOLLOW UP CODE VIOLATION

Date Description Inspector Results Comments
06/30/2003 FOLLOW UP CODE VIOLATION Approved ATTENDED COURT WITH MS. SITA & INSP. II RICK SALDATE. MR CAMPAS DID NOT APPEAR. ITEMS TO HAVE BEEN ABATED WERE EXPIRED ELECTRICAL PERMIT. COURT FINED MR. CAMPAS 10,000.00 $. CASE WAS REFERED TO PROSECUTORS OFFICE FOR FAILURE TO ABATE.
06/16/2003 FOLLOW UP CODE VIOLATION Approved 14 DAY EXTENSION FOR 6/30/03 @ 3:30 PM CONTINUANCE GRANTED. IF NO ACTION TAKEN OWNER WILL BE FINED.
05/14/2003 FOLLOW UP CODE VIOLATION Approved ALL PARTIES APPEARED. MR. CAMPAS HAS PULLED COMBO PERMITS FOR WATER HEATER ENCLOSER & MECHANICAL PERMIT FOR WALL FURNACE. HAS REMOVED HARARDOUS PORCH STRUCTURE. MR. CAMPAS HAS MET CONDITIONS SET FOR THIS COMPLINCE HEARING. PROSAECUTOR AGREEDED TO CONTINUE HEARING FOR JUNE 16TH 2003 AT 10:00 AM. OWNER TO HAVE COMPLETED ELECTRICAL, HAZARDOUS PLUMBING & HOT WATER HEATERS.
05/13/2003 FOLLOW UP CODE VIOLATION Approved MET OWNER ON SITE FOR FOLLOW UP INSPECTION, PRIOR TO COURT APPEARANCE. HAZARDOUS PORCH HAS BEEN REMOVED. VIOLATION UNABATED ARE AS FOLLOWS.(1) EXPIRED ELECTRICAL PERMIT-NO FINAL.(2) UNIT 1 & 3 LACKING WORKING SMOKE DETECTOR.(3) INSTALLATION OF NEW FURNACE IN UNIT 1 & 3 LACKING PERMITS. (4) G.F.I.C. TEST SHOWING OPEN GROUND IN UNIT 3. OWNER STATED HE WOULD HAVE SMOKE DETECTORS WORKING AND PERMITS FOR HOT WATER HEATER ENCLOSER & PERMIT FOR NEW FURNANCE THIS AFTERNOON ALSO WILL ABATE OPEN GROUNDS IN UNIT3. WILL CALL WHEN ISSUES ARE ABATED.

RECIVED CALL FROM OWNER. PROPERTY IS READY FOR INSP. ARRIVIED ON SITE, OWNER STATES REQUIRED PERMITS HAVE BEEN ISSUED. CHECKED SMOKE DETECTORS IN UNITS 1 & 3 BOTH OPERATIONAL. OPEN GROUNDS HAVE BEEN ABATED IN UNIT 3. WILL CHECK PERMITS PLUS FOR ISSUED PERMITS.
04/02/2003 FOLLOW UP CODE VIOLATION Violation OWNER HAD EMERGENCY OUT OF TOWN, DEATH IN THE FAMILY. OWNER ASKED FOR CONTINUANCE. CONTACTED VIOLA, SHE CALLED IN SICK, WILL NOT BE ABLE TO APPEAR. PROSECUTED AGREED TO A CONTINUANCE FOR NEXT WEEK. CONTACTED OWNER-INFORMED HIM CONTINUANCE WAS GRANTED & WILL MEET ON SITE ON 4/4/03 TO GO OVER REMAINING VIOLATIONS TO BE ABATED
03/03/2003 FOLLOW UP CODE VIOLATION Correction Required FOLLOW UP RE INSPECTION:
HECTOR LOPEZ CONDUCTED FOLLOW UP INSPECTION RE COMPLIANCE FOR COURT TODAY. OWNER WAS ON SITE. WAS IN COMPLIANCE IN THAT HE SECURED GAS LINES, INSTALLED HOT WATER HEATER ENCLOSURES AND REMOVED PORCH. IN ADDITION HE HAS PAINTED STRUCTURE, REPLACED ROTTED FACIA.

NOTE: OWNER WILL BE ADDRESSING HOT WATER PERMITS ON NEXT INSPECTION DATE.
03/03/2003 FOLLOW UP CODE VIOLATION Approved VISITED SITE AND MET WITH OWNER. WENT OVER ITEMS REQUESTED BY COURT. HAS REMOVED PORCH HAS SECURED GAS PIPING ON REAR OF STRUCTURE. REPALACED ALL DETERIORATED FACIA BOARD.STRUCTURE HAS BEEN PAINTED.
01/31/2003 FOLLOW UP CODE VIOLATION Correction Required FOLLOW UP INSPECTION:

PROPERTY RE-INSPECTED BY RICK S. AND HECTOR L.

VIOLATION NUMBERS INDICATED ARE ASSOCIATED WITH NOTICE AND ORDER ORIGINALLY ISSUED TO ART APODACA AND TRANSFERED TO MR.CAMPAS WHEN PROPERTY WAS TRASFERED.

1) NON COMPLIANCE: DUE TO PERMITS NOT FINALED.

2) NON COMPLIANCE: DUE TO GAS LINES STILL NOT SECURED. HOT WATER HEATERS NOT ADDRESSED IN THAT NO PERMITS WERE SECURED AND ARE STILL IN DETERIORATED CONDITION. VENT PIPE ASSOCIATED WITH HOT WATER HEATER ON MOST SOUTHERN UNIT STILL TERMINATES IN FRONT OF WINDOW.

3) NON COMPLIANCE: DUE TO EXTERIOR FACIA AND ROOFING MATERIAL STILL HEAVLY DETERIORATED INDICATING NO WORK PERFORMED WHICH WAS ASSOCIATED WITH LEAKING IN THE CIELINGS OF UNITS. WAS NOT ABLE TO GAIN ENTRANCE TO ANY OF THE UNITS INTERIOR.

4) NON COMPLIANCE: DUE TO LACK OF PERMITS FOR ILLEGAL PORCH WHICH DOES NOT CURRENTLY MEET CODE EVIDENCED BY UNDERSIZED BEAM. OWNER ATTEMPTED TO MAKE REPAIRS BY REPLACING SOME ROTTED SHEATHING AND LAYING ROOFING MATERIAL.

5) UNIT-1: UNKNOWN: UNABLE TO GAIN ENTRY.

6) UNIT-1: UNKNOWN: UNABLETO GAIN ENTRY. THERE WERE SOME COMPLIANCE ISSUES ON THE PREVIOUS 06/18/02 INSPECTION BUT NOT ALL WERE COMPLIED WITH.

7) UNIT-1: COMPLIANCE. VERIFIED AT EARLY TIME BY INSPECTOR HECTOR LOPEZ.

8) UNIT-1: COMPLIANCE.

9). UNIT-1: COMPLIANCE. ASSOCIATED WITH RE INSPECTION ON 06/18/02.

10) UNIT-2: COMPLIANCE. ASSOCITAED WITH RE INSPECTION ON 06/18/02.

11) UNIT-2: UNKNOWN DUE TO INABILITY TO GAIN ENTRANCE.

12) UNIT-2: UNKNOWN, DUE TO INABILITY TO GAIN ENTRY.

13) UNIT-2: UNKNOWN DUT TO INABILITY TO GAIN ENTRY.

14) UNIT-2: UNKNOWN DUE TO INABILITY TO GAIN ENTRY.

15-17) UNIT-3: UNKNOWN DUE TO INABILITY TO GAIN ENTRY.

18-22) VIOLATIONS ASSOCIATED WITH SOLID WASTE.
01/31/2003 FOLLOW UP CODE VIOLATION Correction Required COURT:

ATTENDED BY RICK S, HECTOR L, AND VIOLA. OWNER FOUND IN NON COMPLIANCE. COMPLIANCE HEARING SET FOR 03/03/03 AT 10:00AM. OWNER MUST COMPLY WITH 1) SECURE GAS LINES, 2) PERMIT AND CORRECT HOT WATER HEATERS. 3) PERMIT OR REMOVE THE FRONT PORCH. OWNER WILL MEET WITH INSPECTOR NEXT WEEK TO WORK OUT COMPLIANCE SCHEDULE.
01/13/2003 FOLLOW UP CODE VIOLATION Correction Required COURT POSTING:
POSTED COURT MINUTE ON THIS UNIT AS PER MIKE RANKIN. PICTURES IN PACKET AS EVIDENCE. RAY CAMACHO POSTED.
06/18/2002 FOLLOW UP CODE VIOLATION Correction Required COMPLIANCE INSPECTION OF N & O:
ON SITE INSPECTORS WERE RICHARD VIDAL, HECTOR LOPEZ AND JIM HURD.
INITIAL N & O USED AS REF. FOR VIOLATION NUMBERS.
# 1-5: VIOLATION..
#6: COMPLIED WITH LETTERS A, B. LETTER-C IS STILL VIOLATION.
# 7: COMPLIANCE.
# 8: VIOLATION.
# 9: COMPLIANCE.
# 10: COMLIANCE.
# 11-17: VIOLATION.
#18-22: TFD AND SWM ISSUES.

OWNER RELAYED THAT HE TO KEEP THESE UNITS BUT WILL SELL UNITS ASSOCIATED WITH 19 W. DISTRICT (T02VL00487). OWNER ANTICIPATES SUBMITTING PLANS TO WITHIN 2-3 WEEKS FOR BOTH PROPERTIES. HE WILL SELL 19 W. DISTRICT WITH ALL CORRECTIONS MADE.
05/09/2002 FOLLOW UP CODE VIOLATION Correction Required WALKED SITE WITH NEW OWNER. SOME REPAIRS HAVE BEEN COMPLETED SUCH AS WATER BONDING, GAS BONDING, GROUNDING OF SERVICE PANELS. HAS BEGUN WORK ON DOORS (ENTRY) AND WEATHER PROOFING. NEW OWNER HAS ASKED FOR MORE TIME TO COMPLETE REPAIRS. HE WAS REFERRED TO MIKE RANKIN AND INSPECTOR II. ALSO NOTIFIED MIKE RANKIN BY PHONE CALL THAT THE PROPERTY HAS A NEW OWNER. MR. COMPAS (OWNER) IS TO CONTACT US WITH INFORMATION FROM MR RANKIN CONCERNING EXTENTION FOR COMPLETING REPAIRS.
03/15/2002 FOLLOW UP CODE VIOLATION Correction Required VISITED SITE WITH RICHARD VIDAL CHECKED GROUND RODS.2 AND WATER BONDING ALONG WITH GAS PIPE BOND. ALL WERE COMPLETED. 4 NEW SMOKE ALARMS HAVE BEEN INSTALLED. TOOK PICTURE AND WILL DO UPDATE WITH JERRY ORTA ELECTRICAL INSPECTOR SHUT DOWN WILL NO LONGER BE ADVISED.
03/15/2002 FOLLOW UP CODE VIOLATION Correction Required TOOK PICTURES. SABER PROJECT.
03/15/2002 FOLLOW UP CODE VIOLATION Correction Required MET AT SITE AND REVIEWED ELECTRICAL GROUNDING SYSTEMS THAT WERE INSTALLED. BOTH SITES WERE BONDED AT 2-RODS, GAS AND WATER LINES. MET OWNER TO REVIEW SMOKE DETECTORS AND WERE INSTALLED AT WRONG LOCATION AND WOULD BE MOVED BY END OF DAY. OWNER WAS GOING TO BE MOVED BY THE END OF DAY. OWNER WAS GOING TO REMOVE PORCH AND HAS ELECTRICIAN WORKING ON OTHER ISSUES THAT NEED TO BE ADDRESSED AND HAS BEEN IN CONTACT WITH HECTOR LOPEZ. UNIT THAT WAS ADDED WAS VACANT BUT BEING WORKED ON. HECTOR WILL DO F/U.
03/12/2002 FOLLOW UP CODE VIOLATION Denied SUMMARY OF VIOLATION: EAST BUILDING (1-5)


COMPLEX VIOLATIONS:
1) UHC 301& 1001.5: WORK W/O PERMITS & HAZ ELECTRICAL.
THE MAIN SERVICE HAS BEEN INSTALLED W/O PERMITS AND NOT UP TO CODE. THE CIRCUITS ARE INADEQUATE FOR LOAD.

CORRECTIONS REQUIRED: COMMERCIAL UPGRADE SERVICE. ALL GROUNDING & BONDING MUST BE INSTALLED. EACH UNIT WILL REQUIRE A MIN OF 4-CIRCUITS (2-KITCHEN WITH ONE GFCI PROTECTED, 1 FOR LIGHTING AND 1 FOR HEATING & COOLING). ALL WORK WILL REQUIRE LICENSED ELECTICAL CONTRACTOR WITH L-11 LICENSE. LETTER HEAD WITH COMPANY NAME NEEDS TO BE SUBMITTED. DOCS TO BE SUBMITTED WILL BE FLOORPLAN FOR ELECTRICAL LAYOUT. TEP TO PROPERLY CONNECT SERVICE.

2) UHC 301 & 1001.6: HAZARDOUS PLUMBING:
THE MAIN GAS LINE (MASTER METER) HAS DETERIORATED TO THE POINT OF DISATTACHING FROM SECUREMENT. THE HOT WATER HEATERS HAVE DETERIORATED AND NOT MAINTAINED TO CODE (EVIDENCED BY INCORRECT SHUT OFF VALVES & FLEX LINES) TO THE POINT OF NECESSITATING CODE REQUIREMENT REPAIRS UNDER PERMIT.

CORRECTIONS REQUIRED: RESECURE MAIN GAS LINE TO CODE. SECURE PLUMBING PERMIT FOR HOT WATER HEATERS.

3) UHC 1001.3(6) & 1001.8(4): STRUCTURAL HAZ & FAULTY WEATHER PROTECTION:
DETERIORATION OF ROOF HAS ALLOWED WATER PENETRATION EVIDENCED BY WATER STAINAGE IN THE INTERIOR CIELINGS.

CORRECTIONS REQUIRED: REPAIR ROOF SO THAT STRUCTURE IS WEATHER PROTECTED.

4) UHC 301 & 1001.3(6,7): WORK W/O PERMITS & STRUCTURAL HAZ.
THE FRONT PORCH HAS BEEN BUILT W/O PERMITS AND NOT TO CODE. DILAPIDATION AND SAGGING IS EVIDENCED IN THE BEAMS AND RAFTERS.

CORRECTIONS REQUIRED: THE PORCH MUST EITHER BE PERMITTED OR REMOVED.

UNIT-1:

1) UHC 701.3: HEAT:
THE HEATING IS INOPERATIVE AND IN DISREPAIR.

CORRECTIONS REQUIRED: THE HEATING MUST BE PROVIDED.

2) UHC 301 & 1001.5: WORK W/O PERMITS & HAZ ELECTRICAL.
a. COOLER SWITCH IS WIRED TO THE LIGHT SWITCH. b. THE KITCHEN LIGHT FIXTURE HAS BEEN ILLEGALLY ADDED. c. THE GENERAL RECEPTICLE CIRCUITS HAVE A MIX OF TWO AND THREE WIRE RECPTICLES. d. THE SPACE HEATER IS BEING USED IN A HAZARDOUS MANNER IN THAT IT IS THE MAIN SOURCE OF HEAT AND ADDING TO THE OVERLOADED AND ILLEGAL ELECTRICAL SYSTEM.

CORRECTIONS REQUIRED: THE ELECTRICAL VIOLATIONS MUST BE REMOVED, CORRECTED AND/OR INSTALLED UNDER PERMIT.

3) UHC 901: SMOKE DETECTORS:
THE UNIT LACKS REQUIRED SMOKE DETECTORS.

CORRECTIONS REQUIRED: SMOKE DETECTORS MUST BE INSTALLED PER CODE. BATTARY OPERATED SMOKE DETECTORS ARE REQUIRED IN THE HALLWAY.

4) UHC 1001.8(2): WEATHER PROTECTION:
THE FRONT DOOR LACKS SEALS, SWEEPS AND THRESHOLDS.

CORRECTIONS REQUIRED: THE FRONT DOOR MUST BE PROPERLY WEATHER PROTECTED.

5) UHC 801: EXIT:
THE FRONT DOOR HAS A DOUBLE KEY DEAD BOLT.

CORRECTIONS REQUIRED: THE DOUBLE KEY DEAD BOLT MUST BE MODIFIED OR REMOVED.

UNIT-2:

1) UHC 901: SMOKE DET:
THE UNIT LACKS PROPER SMOKE DETECTORS.

CORRECTIONS REQUIRED: INSTALL SMOKE DETECTOR IN THE HALL AREA.

2) UHC 701.3: HEAT:
THE UNITS FURNACE IS INOPERABLE AND NOT MAINTAINED.

CORRECTIONS REQUIRED: REPAIR HEATING.

3) UHC 1001.3(6): STRUCTURAL:
THE WALL BEHIND THE KITCHEN STOVE HAS A LARGE HOLE AND IS IN DISREPAIR.

4) UHC 1001.8(2): WEATHER PROTECTION:
THE FRONT DOOR DOES NOT SEAL PROPERLY AND THE KITCHEN WINDOW CONTAINS A BROKEN WINDOW.

5) UHC 1001.2(7): SANITATION:
THE BATHROM WINDOW DOES NOT OPERATE, NOT MEETING THE REQUIRED VENTILATIING.

UNIT-3:

1) UHC 701.3: HEATING:
THE FURNACE IS INOPERABLE AND HAS NOT BEEN MAINTENED PROPERLY.

CORRECIONS REQUIRED: REPAIR HEATING.

2) UHC 901: SMOKE DETECTORS:
THE UNIT LACKS SMOKE DETECTORS.

CORRECTIONS REQUIRED: INSTALL A SMOKE DETECTOR IN THE HALL AREA.

3) UHC 301 & 1001.5: WORK W/O PERMITS & HAZ ELECTRICAL.
THE KETCHEN LIGHT IS IN DISREPAIR AND ILLEGALLY INSTALLED. THE GENERAL RECEPTICLE CIRCUIT CONTAINS 2 & 3-WIRE RECEPTICLES.

CORRECTIONS REQUIRED: SECURE PERMIT FOR ILLEGAL LIGHT CIRCUIT. MATCH THE PROPER RECEPTICLE FOR THE WIRING SYSTEM.

4) UHC 505.6: SANITATION:
THE BATHROOM DOOR DOES NOT AFFORD PRIVACY IN THAT THE LOCK IS INOPERABLE.

UNIT-4:
UNABLE TO GAIN ENTRY INTO UNIT. WILL CONDUCT F.U. INSPECTION.