Inspection History Details
Inspection Status: Correction Required
Inspection History: INITIAL CODE VIOLATION
Case Number - T02VL00480
Inspection Description - INITIAL CODE VIOLATION
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/07/2002 | INITIAL CODE VIOLATION | Correction Required | SURVEYED FIRE DAMAGE TO THE EXTREME NW. FUEL DISPENSOR AND SURROUNDING AREA, OBTAIN AN ELECTRICAL PLAN AND SHUT OFF ALL DISPENSER CIRCUITS AND FUEL CANOPY ELECRICAL, NOTIFIED MANAGEMENT THAT FUEL DISPENSING WILL REMAIN OFF UNTIL A FINAL HAS BEEN OBTAINED BY THE FIRE DEPT. AND DEVELOPEMENT SERVICES A BARRICADE COMPANY WAS ORDERED TO PROFESIONARY CORDON OFF THE AFFECTED PERIMETER (ALL DISPENSOR. THERE HAS BEEN A RECEPT UPGRADE OF THE FUEL SYSTEM, WITHOUT PERMIT. OR INSPECTIONS. THERE IS FUEL LEAKING FORM SOME FITTING REASON FOR COMPELTE BARRICADE SOME CRITICAL ELECTRICAL DESCREPANCIES. THREADED PLUGS FOR EXPLOS. PROOF BOXES LOOSE AND MISSING, EQUIPMENT GROUND TO DISPENSOR CUT AND RESIDENTIFIED AND USED AS UNGROUNDED CONDUCTORS WITH REMAINDER OF EQUIPMENT GROUND SYSTEM UNATTACHED. THIS WAS A RANDOM SAMPLEING OF 3 UNITS. HAND DELIVERED NOTICE OF 3/7/02 FU 4/7/02 |