Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T02VL00480

Parcel: 132130550


Addresses:

3601 S PARK AV


Inspection Status: Correction Required

Inspection History: INITIAL CODE VIOLATION

Case Number - T02VL00480

Inspection Description - INITIAL CODE VIOLATION

Inspection Status - Correction Required

Date Description Inspector Results Comments
03/07/2002 INITIAL CODE VIOLATION Correction Required SURVEYED FIRE DAMAGE TO THE EXTREME NW. FUEL DISPENSOR AND SURROUNDING AREA, OBTAIN AN ELECTRICAL PLAN AND SHUT OFF ALL DISPENSER CIRCUITS AND FUEL CANOPY ELECRICAL, NOTIFIED MANAGEMENT THAT FUEL DISPENSING WILL REMAIN OFF UNTIL A FINAL HAS BEEN OBTAINED BY THE FIRE DEPT. AND DEVELOPEMENT SERVICES A BARRICADE COMPANY WAS ORDERED TO PROFESIONARY CORDON OFF THE AFFECTED PERIMETER (ALL DISPENSOR. THERE HAS BEEN A RECEPT UPGRADE OF THE FUEL SYSTEM, WITHOUT PERMIT. OR INSPECTIONS. THERE IS FUEL LEAKING FORM SOME FITTING REASON FOR COMPELTE BARRICADE SOME CRITICAL ELECTRICAL DESCREPANCIES. THREADED PLUGS FOR EXPLOS. PROOF BOXES LOOSE AND MISSING, EQUIPMENT GROUND TO DISPENSOR CUT AND RESIDENTIFIED AND USED AS UNGROUNDED CONDUCTORS WITH REMAINDER OF EQUIPMENT GROUND SYSTEM UNATTACHED. THIS WAS A RANDOM SAMPLEING OF 3 UNITS. HAND DELIVERED NOTICE OF 3/7/02 FU 4/7/02