Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/14/2003 | PLUMBING - FINAL | Approved | ||
| 05/13/2003 | PLUMBING - FINAL | Denied | REVIEWED JOINT SEWER AGREEMENT OK 2.) CONTRACTOR TO INSURE AT LEAST 12" OF COVER OVER ABS. 3.) TEST BALL FAILED WATER TEST FOR SEWER TO BE FROM LOWEST TO HIGHEST POINT. SOME FITTINGS APPROVED TO BE DAMP. CHECK FOR POSSIBLE LEAKS. |
|
| 05/01/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1.) 3" SEWER LINE REQUIRES 1/4" PER FT OF GRADE. THERE ARE SOME FLAT AREAS CHECK GRADE ON ENTIRE RUN SEE SECTION: 718.1 94 UPC. 2.) WILL REQUIRE A JOINT MAINTENANCE AGREEMENT AND RECORDED WITH THE COUNTY CAN CONNECT TO THE SAME HCS PROVIDE THIS FORM ON SITE @ TIME OF INSPECTIONS. 3.) CAN NOT HAVE A THREADED FITTING UNDERGROUND OR NON -ACCESSIBLE LOCATION. SEE SECTION: 316.1.5. 94 UPC 4.) ABS REQUIRES MIN OF 12" OF COVER. |