Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) PROVIDE PERMIT FOR PITCHED ROOF OVER FLAT ROOF. 2.) VENT TERMINATION INSIDE ATTIC NOT APPROVED. 3.) FLEX CONNECTORS FOR STOVE AND WATER HEATER UNDERSIZED 4.) T & P RELIEF TER MINUS ABOVE ALLOWABLE TWO FEET AFG 5.) REMOVE TEE AND USE COUPLING ON GAS RISER. 6.) SEE TABLE 3-1 94UPC SUPPORT OF HORIZONTAL GAS PIPING 7.) WHERE UNIONS ARE NECESSARY, USE A RIGHT LEFT NIPPLE AND COUPLING. |
|
| 12/31/2002 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) PLEASE HABE YOUR PLUMBER PROVIDE PRESSURE TEST ON COMPLETE SYSTEM OF NOT LESS THEN 10 POUNDS 2) CALL AGAIN WHEN READY |