Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/26/2002 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* | |
| 12/23/2002 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection 0000* | |
| 12/19/2002 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection 0000*NEEDS TO COMPLETE RISER AT METER PRIME & WRAP JOINT TEST & CALL INSPECTION 1" AT METER SET. | |
| 12/17/2002 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*1.) YOU MUST USE TAPE PRIMER & 10 MIL TAPE ON ALL BURIED JOINTS. 2.) PIPE MUST BE MIN 12" DEEP & SITTING ON A FIRM BED. 3.) EXTEND RISER AT GAS METER LOCATION PROVIDE MIN. 10LB TEST RECALL FOR INSPECTION APPLIANCES INSIDE HOME ARE OK ONLY CORRECTIONS ARE OUTSIDE. |