Permit: T02PL02325

Parcel: 10605005E


Addresses:

3845 N ORACLE RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02PL02325

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/09/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*
1.) FOR THE PLUMBERS REFERENCE: APPLY TAPE PRIMER TO CLEAN PIPE AND FITTINGS TO BE WRAPPED. THEN WRAP TIGHTLY, MAKING SURE YOU GET A HALF OVER LAP. STRENTH TIGHTLY AROUND FITTINGS. YOU DO NOT NEED TO REPRIME TAPE AFTER WRAPPED.
2.) CORRECTION MADE OK
3.) PLAN AND APPARATUS APPROVED BY EXAMINER
4.) OK FOR GAS.
5.) UCC LEFT AT METER. SW GAS 889-1888.
12/17/2002 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*
1.) PLEASE PROVIDE APPROVED DRAWING WITH TOTAL LENGTH & TOTAL BTU'S FOR EACH FIXTURE.
2.) PLEASE PROVIDE APPROVED CLEVIS HANGERS
REMOVE PLUMBERS PLUMBER TAPE.
3.) GAS LINE TO BE 6: ABOVE GRADE OR 12" BELOW
4.) PLEASE PRIME & WRAP ALL GAS PIPING. UNDERGROUND W/10MIL TAPE.