Permit: T02PL02154

Parcel: 131010250


Addresses:

4828 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02PL02154

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/19/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK
2.) GAS SHUT OFF VALVES OK
3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK.
12/12/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*
1.) APPROVED DRAWING SHOWS 1 1/2 ALL THE WAY TO DEEP FRYER.
2.) APPROVED DRAWING DOSE NOT SHOW FULL DEVELOPED LENGTH AS REQUESTED ON NOTE #1
3.) MUST SEAL PENETRATION OF GAS LINE GOING INTO BLDG.
12/06/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*
1.) MUST PROVIDE BTU & CFH DEMAND AND DRAWING ON GAS SYSTEM SHOWING DEVELOPED LENGTH.
2.) WATER HTR P & T DRAIN CAN NOT HAVE A FLEX LINE
3.) WATER HTR FLU VENT MUST BE SCREWED DOWN WITH (3) SHEET METAL SCREWS PER JOINT.