Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02PL02154
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK. |
|
12/12/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* 1.) APPROVED DRAWING SHOWS 1 1/2 ALL THE WAY TO DEEP FRYER. 2.) APPROVED DRAWING DOSE NOT SHOW FULL DEVELOPED LENGTH AS REQUESTED ON NOTE #1 3.) MUST SEAL PENETRATION OF GAS LINE GOING INTO BLDG. |
|