Permit: T02PL02038

Parcel: 12218122E


Addresses:

1414 N DODGE BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/14/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE LEFT GAS CARD.
11/13/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*
1.) 19 PSI PRESSURE TEST IS OK.
2.) WATER HEATER VENT IS NOT TO CODE SINGLE WALL VENT PIPE CANNOT BE CONCEALED INSIDE A WALL OR CEILING SPACE. USE DOUBLE WALL PIPE BETWEEN CEILING & ROOF & EXTEND TO 3' ABOVE EVAP COOLER. USE LISTED ROOF JACK & CAP.
3.) PROVIDE AN AGA APPROVED SHUT OFF VALVE AT WALL HEATER.

RECALL FOR INSPECTION.