Permit: T02PL01951

Parcel: 129091000


Addresses:

1408 E 27TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/14/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*CORRECTION MADE OK.
OK FOR GAS.
UCC LEFT AT METER.
11/13/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) REQUIRED MINIMUM 10# AIR TEST TEST DOWN AT THIS TIME.
11/05/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) WHERE UNIONS ARE NECESSARY A RIGHT LEFT NIPPLE AND COUPLING SHALL BE USED.
11/04/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) UNDERGROUND GAS PIPING REQUIRES A MINIMUM OF TWELVE INCHES OF COVER. 2.) VENT CAP ON FLUE NOT APPROVED. 3.) WATER HEATER ENCLOSURE NOT SECURED TO WALL 4.) T&P RELIEF DRAIN LEAKING REPLACE VALVE.
10/31/2002 PLUMBING - FINAL Denied IVRS - Inspection 0000*1.) GAS PIPE COVERED WITHOUT INSPECTION ON PER MISSION. 2.) APPLIANCE CONNECTOR CANNOT PASS THROUGH JACKET OF WH ENCLOSURE.