Permit: T02PL01926

Parcel: 12904269A


Addresses:

2009 E 14TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/20/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*13 PSI TEST.
REMOVE UNION FROM GAS LINE ON ROOF USE REVERSE THREAD COUPLING & NIPPLE. RETEST SYSTEM.
02/19/2003 PLUMBING - FINAL Partial Approval IVRS - Inspection 0000*
02/12/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*
1.) GAS FLEX TO FURNACE CANNOT EXCEED 3' IN LENGTH.
2.) REPLACE GAS SHUT OFF VALVES TO FURNACE USE AGA APPROVED VALVES.
3.) PROVIDE A ROOF JACK WHERE GAS PIPE PENETRATES THE ROOF.
4.) BLOCK & CLAMP GAS PIPE ON ROOF.
5.) PROVIDE MIN. 10 LB. TEST ON GAS SYSTEM. RECALL FOR INSPECTION.