Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02PL01833
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1.) OK TO DRYWALL PATCH EXSISTING WALL 2.) NOTE: INDIRECT WASTE OUTLET MUST HAVE 1" AIR GAP @ FLOOR SINK. | |
10/16/2002 | PLUMBING - FINAL | Partial Approval | 1.) SOIL WATER TEST IS OK 2.) P.O.C. OF NEW 3" BLDG. SEWER TO EXSISTING HCS CONNECTION IS OK 3.) OK TO BACKFILL TRENCH. 4.) NOTE: WILL REQUIRE 12" OF COVER WHERE BLDG. SEWER & BLDG. DRAIN CONNECT. | |
10/15/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) MUST PROVIDE VENT FOR FLOOR SINK AND C.O. 2.) ABS BLDG. SEWER REQUIRES 12" OF COVER OR USE CAST IRON MATERIAL UNTIL YOU CAN GET 12" OF COVER THEN RUN ABS. 3.) 3" BLDG. SEWER REQUIRES 1/4" PER FT. OF GRADE 4.) DO NOT COVER. |