Permit: T02PL01657

Parcel: 132102460

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02PL01657

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) ALL CORRECTION MADE OK 2.) OK FOR GAS 3.) UCC LEFT AT METER. 4.) SW GAS 889-1888.
09/24/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) NO TEST ON GAS PIPING REQUIRES MINIMUM #10 TEST. 2.) CAP OFF ABANDONED GAS PIPING. 3.) CONNECT WATER HEATER GAS PIPING COMPLETE. 4.) CODE REQUIRES THAT UNDERGROUND GAS PIPING HAVE AT LEAST 12" COVER.
09/16/2002 PLUMBING - FINAL Denied IVRS - Inspection 0000*TEST COMPLETE SYSTEM. 2.) REPLACE P & T VALVE IN WATER HEATER 3.) REMOVE FLEXABLE APPLIANCE CONNECTOR FROM PASSING THROUGH DRYWALL & FURANCE JACKET & REPLACE WITH STEEL PIPE. 4.) FIRE PLACE REQUIRES VALVE OUTSIDE FINE BOX IN ROOM WITH FIRE PLACE.