Permit: T02PL01609

Parcel: 122131780

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T02PL01609

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/09/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000* 1)SOIL WATER TEST IS OK 2) ALL CORRECTIONS HAVE BEEN MADE 3) OK TO BACKFILL TRENCH
10/08/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) SEE NOTE #3 AS REQUESTED 2.) DO NOT COVER.
10/04/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) MUST USE PROPER GLUE ON ABS FITTINGS @ WEST DWELLING AS REQUESTED. PLUMBER PAINTED ABS GLUE OVER THESE JOINTS. 2.) MUST PAY REINSPECTION FEE PRIOR TO NEXT INSPECTION. 3.) RE-TEST NEW FITTINGS THAT WERE INSTALLED 4.) DO NOT COVER.
10/02/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) CAN NOT USE TWO WAY C.O. FITTING WITH A EXTENSION ON IT. MUST USE (2) DIRECTIONAL FITTING FOR TWO WAY C.O. 2.) CAN NOT USE SCREEN TRANSITION GLUE FOR ABS @ WEST DWELLING TRANSITION GLUE IS ONLY FOR 1 JOINT WHERE SDR-35 CONNECTS TO ABS. 3.) OK TO BACKFILL SEPTIC TANKS ONLY.
09/30/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) PIPING TO BE INSTALLED IN PRACTICAL ALIGNMENT. 2.) BREAK A HOLE IN THE FLOOR OF EACH SEPTIC TANK SO IT WILL NOT RETAIN WATER. 3.) INSTALL APPROVED CLEAN OUT ADAPTERS W/PLUGS AND TRAFFIC RATED CLEAN OUT COVERS IN DRIVE.