Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T02PL01609
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/09/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* 1)SOIL WATER TEST IS OK 2) ALL CORRECTIONS HAVE BEEN MADE 3) OK TO BACKFILL TRENCH | |
10/08/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) SEE NOTE #3 AS REQUESTED 2.) DO NOT COVER. | |
10/04/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) MUST USE PROPER GLUE ON ABS FITTINGS @ WEST DWELLING AS REQUESTED. PLUMBER PAINTED ABS GLUE OVER THESE JOINTS. 2.) MUST PAY REINSPECTION FEE PRIOR TO NEXT INSPECTION. 3.) RE-TEST NEW FITTINGS THAT WERE INSTALLED 4.) DO NOT COVER. | |
10/02/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) CAN NOT USE TWO WAY C.O. FITTING WITH A EXTENSION ON IT. MUST USE (2) DIRECTIONAL FITTING FOR TWO WAY C.O. 2.) CAN NOT USE SCREEN TRANSITION GLUE FOR ABS @ WEST DWELLING TRANSITION GLUE IS ONLY FOR 1 JOINT WHERE SDR-35 CONNECTS TO ABS. 3.) OK TO BACKFILL SEPTIC TANKS ONLY. | |
09/30/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) PIPING TO BE INSTALLED IN PRACTICAL ALIGNMENT. 2.) BREAK A HOLE IN THE FLOOR OF EACH SEPTIC TANK SO IT WILL NOT RETAIN WATER. 3.) INSTALL APPROVED CLEAN OUT ADAPTERS W/PLUGS AND TRAFFIC RATED CLEAN OUT COVERS IN DRIVE. |