Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/27/2002 |
PLUMBING - FINAL |
|
Approved |
SOIL WATER TEST IS OK 2.) HCS CONNECTION IS OK 3.) P.O.C. OF NEW BLDG. SEWER TO EXSISTING BLDG. DRAIN IS OK 4.) OK TO BACKFILL TRENCH. |
| 08/23/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MUST EXPOSE HCS CONNECTION 2.) MUST PROVIDE WATER TEST ON BLDG. SEWER FROM C.O. TO HCS CONNECTION @ TIME OF INSPECTION. 3.) 3" BLDG. SEWER REQUIRES 1/4" PER FT. OF GRADE MIN. 4.) CAN NOT HAVE A FERNCO COUPLING UNDERNEATH THE PORCH. 5.) MUST USE SPECIALTY COUPLING OK GLUE COUPLING WHERE NO HUB COUPLING IS. |