Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/15/2002 |
PLUMBING - FINAL |
|
Approved |
1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT, P & T VALVE & DRAIN IS OK 4.) FURNANCE FLU VENT IS OK. |
| 08/14/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*) 1.) FULL DEVELOPE LENGTH MEANS FROM THE GAS SHUT OFF VALVE TO THE REGULATOR (MAX 3'-0". |
| 08/13/2002 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*SHUT OFF VALVE FOR FURNACE MUST BE WITHIN 3'-0" MAX OF DEVELOPED LENGTH 2.) MUST SEAL PENETRATION OF GAS LINE @ SOUTH WALL 3.) GAS PRESSURE TEST MUST BE. RETESTED. |