Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date |
Description |
Inspector |
Results |
Comments |
| 08/17/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Approved |
IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK 2.) ALL CORRECTIONS HAVE BEEN MADE 3.) OK TO BACKFILL TRENCH. |
| 08/12/2002 |
PLUMBING - GAS PRESSURE TEST |
|
Denied |
IVRS - Inspection 0999*1.) PE YARD GAS PIPING HAS BEEN COVERED AND WAS INSTALLED WITHOUT PROPER TRACER WIRE SEE SECTION: 1211.16 94UPC EXPOSE ENTIRE LINE. 2.) PE YARD GAS PIPE MUST HAVE MIN 18" OF COVER SEC SECTION 1211.5 94 UPC. 3.) GAS SYSTEM IS NOT INSTALLED AS PER APPROVED PLANS 4.) THERE IS A LEAK IN SYSTEM @ 1 1/2" COUPLING BETWEEN THE RUN FROM WEST TO EAST. 5.) RE TEST SYSTEM 6.) MUST SCREW DOWN FLU VENT TO WATER THTR COLLAR WITH (3) SHEET METAL SCREWS. |