Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/15/2002 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) GAS PRESSURE TEST IS OK 2.) GAS SHUT OFF VALVES OK 3.) WATER HTR FLU VENT, P & T DRAIN IS OK 4.) FURNACE FLU VENT IS OK. |
| 08/13/2002 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) MUST REMOVE THREAD PROTECTED IN GAS LINE AND REPLACE WITH APPROVED COUPLINGS 2.) MUST REMOVE UNION @ HOUSE CONNECTION AND REPLACE WITH SOLID PIPE BE ADD A AGA SHUT OFF VALVE BEFORE THE UNION. 3.) MUST SCREW DOWN WATER HTR FLU VENT WITH (3) SHEET METAL SCREWS PER JOINT AND @ COLLAR. 4.) MUST PROVIDE A 3/4" P&T VALVE AND DRAIN EXSISTING WATER HTR DOES NOT HAVE APPROVED P &T VALVE OR DRAIN MUST FILE FOR A VERIANCE WITH CODES ADMINSTRATOR. 5.) RETEST SYSTEM 10LBS MIN. 6.) MUST REPLACE GAS SHUT OFF VALVES WITH AGA OR CSA SHUT OFF VALVES 7.) OK TO BACKFILL TRENCH BUT LEAVE FITTINGS EXPOSED. |